Phasor Measurement Units Optimal Placement and Performance Limits for Fault Localization

Raksha Ramakrishna


Citation

Jamei, M., Ramakrishna, R., Tesfay, T., Gentz, R., Roberts, C., Scaglione, A., & Peisert, S. (2019). Phasor Measurement Units Optimal Placement and Performance Limits for Fault Localization. IEEE Journal on Selected Areas in Communications.

Abstract

In this paper, the performance limits of faults localization are investigated using synchrophasor data. The focus is on a non-trivial operating regime where the number of Phasor Measurement Unit (PMU) sensors available is insufficient to have full observability of the grid state. Proposed analysis uses the Kullback Leibler (KL) divergence between the distributions corresponding to different fault location hypotheses associated with the observation model. This analysis shows that the most likely locations are concentrated in clusters of buses more tightly connected to the actual fault site akin to graph communities. Consequently, a PMU placement strategy is derived that achieves a near-optimal resolution for localizing faults for a given number of sensors. The problem is also analyzed from the perspective of sampling a graph signal, and how the placement of the PMUs i.e. the spatial sampling pattern and the topological characteristic of the grid affect the ability to successfully localize faults. To highlight the superior performance of presented fault localization and placement algorithms, the proposed strategy is applied to a modified IEEE 34, IEEE-123 bus test cases and to data from a real distribution grid. Additionally, the detection of cyberphysical attacks is also examined where PMU data and relevant Supervisory Control and Data Acquisition (SCADA) network traffic information are compared to determine if a network breachhasaffectedtheintegrityofthesysteminformationand/or operations.

Related Videos

Related Research Themes

Related Research Activities

Related Technologies

Related Impact Areas

CREDC Authors

Copyright Notice

This material is presented to ensure timely dissemination of scholarly and technical work. Copyright and all rights therein are retained by authors or by other copyright holders. All persons copying this information are expected to adhere to the terms and constraints invoked by each author's copyright. In most cases, these works may not be reposted without the explicit permission of the copyright holder.

  1. The following copyright notice applies to all of the above items that appear in IEEE publications: "Personal use of this material is permitted. However, permission to reprint/publish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution to servers or lists, or to reuse any copyrighted component of this work in other works must be obtained from IEEE."

  2. The following copyright notice applies to all of the above items that appear in ACM publications: " ACM, effective the year of publication shown in the bibliographic information. This file is the authors version of the work. It is posted here by permission of ACM for your personal use. Not for redistribution. The definitive version was published in the journal or proceedings indicated in the bibliographic data for each item."

  3. The following copyright notice applies to all of the above items that appear in IFAC publications: "Document is being reproduced under permission of the Copyright Holder. Use or reproduction of the Document is for informational or personal use only."